R410a Air Conditioner Refrigerant Fill, Installation and Maintenance

Content Category

Key Point

1. Must use R410a dedicated tools, accessories, and materials, mustn’t use R22’s  as a substitute.

2. If any refrigerant leak during operation, please ventilate in time. Because if the refrigerant leaks indoor, once it comes into contact with the electric sparks emitted by electric fans, heaters, electric stoves and other appliances, will form toxic gases.

3. When install or move the air conditioner, strictly forbidden to mix air other than R410a refrigerant into the refrigerant circulation system. When air and other gas mixed into the system, the high pressure of the refrigerant circulation system will be abnormal, which is the main cause of the rupture and cracks of the whole system.

4. Don’t mix with other refrigerant or refrigeration oil; otherwise, air conditioner will not cool/heat, the compressor lubrication will deteriorate, generate heat, and even burn out.

R410a Refrigerant

R410a Moisture and Residue

1. R410a compressor (using POE oil), POE oil has stronger water absorption than mineral oil (R22 compressor). When the moisture content of the system exceeds the standard, water will react chemically with POE to generate acid and water, forming a vicious cycle, will destroy the system, generate impurities and copper plating, form sludge, which is the main causes of dirty and oil blockage.

2. Compressor which rubber plug is detached, cann’t be used!

3. When install the outdoor unit, after pulling out the compressor rubber plug, please don’t leave it for a long time (<10minute), and try best to shorten the welding and sealing time of the system (<15minute).

4. When vacuuming, ensure the vacuum degree is < -0.1MPa.

5. Strictly forbidden to leave residues or mix impurities and dust in the system; otherwise, it will block the system, which is one main causes of dirty and oil blockage.

Bell mouth, Nut, Bending Radius

Bell mouth size

Bell Month Size D:(mm), OD=Outer Diameter

 

Copper tube protrusion

Copper tube protrusion A:(mm)

 

Nut size

Nut size B:(mm)

 

Pipe bending radius

Pipe bending radius R: (mm)

Vacuum

Vacuuming

Vacuum Method

R410a Fill

Refill R410a after Partial Refrigerant Leakage

1. Must add R410a, not R22

2. Needn’t release the remaining refrigerant in the air conditioner, just add it in liquid form.

Since R410a is a near-azeotropic mixed refrigerant, when adding it in gas form, the composition of the refrigerant will change, resulting in poor performance of the air conditioner.

R410a Inverter Air Conditioner Charging Method

Add refrigerant in forced cooling mode!

In this mode, compressor frequency is fixed and the suction pressure is relatively stable, which makes it easier to determine whether the charge amount is appropriate.

If the frequency is not fixed, the actual frequency of the compressor is changing, and the tested pressure changes greatly. In this state, adding refrigerant is inaccurate.

Facebook
Twitter
LinkedIn
Reddit
Print

Leave a Reply

About Our Company

China Speedway Group is a professional HVACR products’ manufacturer and wholesaler, we customize different HVACR products and spare parts, especially refrigeration products and parts. Such as air conditioning, refrigeration equipment, cold room solution, ice machine, dehumidifier, electric motor, heat exchanger,copper coil, etc.

As worked in HVACR field since 2010, we have more experiences can provide you unique products and solutions, also will supply life-span free charge of technical support. Warmly welcome inquiry us with your sample, drawing or design, our aim is making your idea come true and benefit you. 

What’s more, for our clients, we will source other products, verify the supplier, negotiate with them with free charge for you.

About Author

Picture of Vic Cheung
Vic Cheung

Hi, I'm Vic! Start working in HVACR field since 2008, our main products included: air conditioning, cold room refrigeration system, water chiller, ice machine, commercial dehydrator, dehumidifier, heat pump, electric motor, and all accessories. Since joined China Speedway Group in 2012, I worked in here more than 10 years, as the general manager of export department, we have established 50+ agent in different countries and areas.
As our experience and strong technical support, we can solve your issue once you have, and our chief engineer has worked in HVACR field since 1997. I am so proud of our knowlege is more and more popular not only for engineer, and for HVACR business new comer, DIY lovers. Hope you are enjoying our articles, if any question or comments just welcome to send me marketing at cn-beyond.com

All Posts

Contact Us

Just fill out your email address, phone and a brief description of your inquiry in this form. We will contact you within 24 hours.

Contact Us

Ready to Start Your Project Wth Us?

Partner with us to increase your brand reputation, get an impressive experience for your clients to remember you lifelong, and help you stand out in the competitive market !

Don’t Miss Out on the Best OEM Partner!

Ready to Work With Us?

Experience our difference and Take the first step toward a better future for your business!