Partagez des solutions optimales, connaissances professionnelles en CVC et actualités de l'industrie

Comment juger la charge correcte de réfrigérant?

Catégorie de contenu

Whether the refrigerant charge of équipement de réfrigération is too much or too little, it will cause facility abnormality, tel que: decreased cooling capacity & EER, shortened equipment life, increased input power, etc.. So how can we judge whether the refrigerant charge is correct ?

Some commonly used judgment methods as follow:

Touch Compressor Pipeline by Hand

Everyone feels hot or cold differently. Généralement, the human body feels hot when the temperature is >37℃, and feels cold when the temperature is <37℃. The temperature limit of skin perception is 49℃.

When you touch compressor suction and discharge pipe and feel that they aren’t cold enough, that means the refrigerant charge isn’t enough.

Touch compressor pipeline

Watch Sightglass Bubble

Bubble indicates refrigerant absence and loss of liquid line pressure. If the liquid line pressure loss is severe, the liquid refrigerant will quickly evaporate into gas. This gas will reduce refrigerant flow when flowing through the Soupape de détente (TXV) and cause its damage. If the system is not cooled enough, the pressure loss can easily cause bubbles in the sight glass.

sightglass see bubble

Test Refrigerant High-Low Pressure

Premièrement, you must ensure both condensation air volume and evaporation air volume meet the international standard. If the two fail to match, it will directly affect the accuracy of the refrigerant pressure test.

test refrigerant high low pressure

Test Compressor Current

Compressor current will behave differently in different situations. Par exemple, it will be affected by the main power voltage value, a small deviation in voltage may cause a significant deviation in current.

En outre, the current is also subject to the lubrication condition of the motor bearings and changes in temperature.

Test compressor current

Calculate Superheat

Calculate superheat by measuring the suction temperature & pressure of suction pipe on the évaporateur. The pressure value is converted into temperature value, then minus suction temperature value, the difference is called superheat.

For the capillary system, measure the correct capillary flow depends on the pressure and resistance. For the expansion valve system, it is easy to overcharge. Since the expansion valve will automatically open and close.

The superheat of the expansion valve system is 7~8℃.

Surchauffer

 

Calculate Subcooling

Calculate Subcooling by measuring the liquid temperature & pressure values ​​on the liquid pipe. The pressure value is converted into temperature value, then minus liquid temperature value, the diference is subcooling, which is equivalent to the condensation degree of the refrigerant liquid in the condenser.

If subcooling is low or non-existent, you can see the bubbles (caused by the drop in liquid pipe pressure) in the sight glass. The subcooling of the expansion valve system is 8~12℃. Subcooling degree only represents the condensation effect.

Subcooling

Calculate Inlet and Outlet Air Volume Temperature Difference

Temperature difference of air-cooled condenser is 16.7℃, and temperature difference of the evaporator is 11.1℃. Under high latent heat load, évaporateur “△twill decrease. So excessive injection, in order to obtain a higher△t”, will be detrimental to compressor operation.

Since the air volume will affect△t”, the condenser and évaporateur air volumes must be correct before measuring△t”.

Temperature gap

Suction Pipe Condensation

This method depends on the refrigerant liquid flow rate of the capillary tube and the pressure difference at both ends.

If the evaporator air volume is normal, the refrigerant flows through the evaporator according to the load change, and no frost will form. If the load decreases, the liquid refrigerant will flow through the évaporateur and enter the suction pipe.

The water vapor in the surrounding air will condense on the copper tube, iIf there is enough liquid refrigerant.

Condensation

Weigh Charge

Weighing is the most effective way to calculate refrigerant charge!

D'abord, recover refrigerant, then evaculate the refrigeration system, and finally refilled by weighing.

This method is the most accurate no matter what kind of refrigeration system it is.

Weigh charge

Tout commentaire?

Bienvenue laisser un message ou reposter.

Facebook
Twitter
LinkedIn
Reddit
Imprimer

Laisser un commentaire

Au sujet de notre compagnie

Groupe China Speedway est un produit professionnel HVACR’ fabricant et grossiste, nous personnalisons différents produits et pièces de rechange HVACR, en particulier les produits et pièces de réfrigération. Comme la climatisation, équipement de réfrigération, solution chambre froide, machine à glace, déshumidificateur, moteur électrique, échangeur de chaleur,bobine de cuivre, etc..

Comme travaillé dans le domaine HVACR depuis 2010, nous avons plus d'expériences pouvons vous fournir des produits et des solutions uniques, fournira également des frais de support technique gratuits pendant toute la durée de vie. Nous souhaitons la bienvenue avec votre échantillon, dessin ou conception, notre objectif est que votre idée devienne réalité et vous profite.

Quoi de plus, pour nos clients, nous nous procurerons d'autres produits, vérifier le fournisseur, négocier avec eux gratuitement pour vous.

à propos de l'auteur

Image de Vic Cheung
Vic Cheung

Salut, je suis Vic! Commencer à travailler dans le domaine HVACR depuis 2008, nos principaux produits inclus: climatisation, système de réfrigération de chambre froide, refroidisseur d'eau, machine à glace, déshydrateur professionnel, déshumidificateur, pompe à chaleur, moteur électrique, et tous les accessoires. Depuis qu'il a rejoint China Speedway Group en 2012, J'ai travaillé ici plus de 10 années, en tant que directeur général du département export, nous avons établi 50+ agent dans différents pays et régions.
Comme notre expérience et notre solide support technique, nous pouvons résoudre votre problème une fois que vous avez, et notre ingénieur en chef a travaillé dans le domaine HVACR depuis 1997. Je suis tellement fier de notre connaissance est de plus en plus populaire non seulement pour les ingénieurs, et pour le nouveau venu dans l'entreprise HVACR, Amateurs de bricolage. J'espère que vous appréciez nos articles, si vous avez des questions ou des commentaires, n'hésitez pas à m'envoyer du marketing sur cn-beyond.com

Tous les messages

Contactez-nous

Remplissez simplement votre adresse e-mail, téléphone et une brève description de votre demande dans ce formulaire. Nous vous contacterons dans 24 heures.

Contactez-nous

Prêt à démarrer votre projet avec nous?

Associez-vous à nous pour augmenter la réputation de votre marque, obtenez une expérience impressionnante pour que vos clients se souviennent de vous toute leur vie, et vous aider à vous démarquer sur le marché concurrentiel !

Ne manquez pas le meilleur partenaire OEM!

Prêt à travailler avec nous?

Vivez notre différence et faites le premier pas vers un avenir meilleur pour votre entreprise!