Whether the refrigerant charge of холодильное оборудование is too much or too little, it will cause facility abnormality, такой как: decreased cooling capacity & ЭОР, shortened equipment life, increased input power, и т. д.. So how can we judge whether the refrigerant charge is correct ?
Some commonly used judgment methods as follow:
Touch Compressor Pipeline by Hand
Everyone feels hot or cold differently. Обычно, the human body feels hot when the temperature is >37℃, and feels cold when the temperature is <37℃. The temperature limit of skin perception is 49℃.
When you touch compressor suction and discharge pipe and feel that they aren’t cold enough, that means the refrigerant charge isn’t enough.
Watch Sightglass Bubble
Bubble indicates refrigerant absence and loss of liquid line pressure. If the liquid line pressure loss is severe, the liquid refrigerant will quickly evaporate into gas. This gas will reduce refrigerant flow when flowing through the расширительный клапан (ТХВ) and cause its damage. If the system is not cooled enough, the pressure loss can easily cause bubbles in the sight glass.
Test Refrigerant High-Low Pressure
Во-первых, you must ensure both condensation air volume and evaporation air volume meet the international standard. If the two fail to match, it will directly affect the accuracy of the refrigerant pressure test.
Test Compressor Current
Compressor current will behave differently in different situations. Например, it will be affected by the main power voltage value, a small deviation in voltage may cause a significant deviation in current.
Кроме того, the current is also subject to the lubrication condition of the motor bearings and changes in temperature.
Calculate Superheat
Calculate superheat by measuring the suction temperature & pressure of suction pipe on the испаритель. The pressure value is converted into temperature value, then minus suction temperature value, the difference is called superheat.
For the capillary system, measure the correct capillary flow depends on the pressure and resistance. For the expansion valve system, it is easy to overcharge. Since the expansion valve will automatically open and close.
The superheat of the expansion valve system is 7~8℃.
Calculate Subcooling
Calculate Subcooling by measuring the liquid temperature & pressure values on the liquid pipe. The pressure value is converted into temperature value, then minus liquid temperature value, the diference is subcooling, which is equivalent to the condensation degree of the refrigerant liquid in the condenser.
If subcooling is low or non-existent, you can see the bubbles (caused by the drop in liquid pipe pressure) in the sight glass. The subcooling of the expansion valve system is 8~12℃. Subcooling degree only represents the condensation effect.
Calculate Inlet and Outlet Air Volume Temperature Difference
Temperature difference of air-cooled condenser is 16.7℃, and temperature difference of the evaporator is 11.1℃. Under high latent heat load, испаритель “△t” will decrease. So excessive injection, in order to obtain a higher “△t”, will be detrimental to compressor operation.
Since the air volume will affect “△t”, the condenser and испаритель air volumes must be correct before measuring “△t”.
Suction Pipe Condensation
This method depends on the refrigerant liquid flow rate of the capillary tube and the pressure difference at both ends.
If the evaporator air volume is normal, the refrigerant flows through the evaporator according to the load change, and no frost will form. If the load decreases, the liquid refrigerant will flow through the испаритель and enter the suction pipe.
The water vapor in the surrounding air will condense on the copper tube, iIf there is enough liquid refrigerant.
Weigh Charge
Weighing is the most effective way to calculate refrigerant charge!
Первый, recover refrigerant, then evaculate the refrigeration system, and finally refilled by weighing.
This method is the most accurate no matter what kind of refrigeration system it is.
Любые комментарии?
Добро пожаловать оставьте сообщение или сделайте репост.