...
Logo đường cao tốc
Chia sẻ giải pháp tối ưu, Tin tức ngành và kiến ​​thức HVACR chuyên nghiệp

How to Run Multiple Cold Rooms With Single Condensing unit?

Mục lục

Running multiple cold rooms with single condensing unit means one outdoor condensing unit supplies refrigerant to two or more evaporators (đơn vị làm mát), typically one evaporator per cold room, through a shared liquid line header and suction header.

This approach can reduce installed cost, tiết kiệm không gian, and simplify maintenance compared with installing a separate condensing unit for each room—when the rooms are compatible in temperature and operating conditions.

The key design requirement is independent room control: each cold room must be able to “call” for cooling without forcing other rooms to overcool or lose control.

When this design works

This design works best when all rooms operate at similar temperature setpoints and therefore can share compatible temperatures (same evaporating temperature “SST”) without major compromises.

If one room is a freezer and another is a cooler, a basic single-circuit shared condensing unit usually struggles because the suction pressure must satisfy the coldest room, and that can cause the warmer room to short-cycle, freeze product, or require special controls beyond a simple setup.

It also becomes risky if the application demands high redundancy (Ví dụ, critical pharmaceutical storage), because one condensing unit becomes a single point of failure for multiple rooms.

Phòng du lịch phòng lạnh 1

Core concept: multiple evaporators with independent control

In a multi-room, single-condensing-unit setup, the condensing unit is the “engine,” and each cold room’s evaporator is a separate cooling zone.

A common and practical way to control each zone is a thermostat in each room that opens/closes a liquid line solenoid valve feeding that room’s evaporator, providing on/off refrigerant flow per room.

This is often paired with a pump-down sequence so the compressor shuts off based on suction pressure after solenoids valve close, which helps prevent liquid refrigerant migration to the compressor during off cycles.

Step-by-step design and installation

Bước chân 1: Confirm temperatures and choose SST

Start by listing each cold room’s target temperature, allowable temperature swing, humidity sensitivity (fresh produce vs frozen foods), and expected door-opening frequency, because these factors drive the evaporator selection and the required SST.

Hiển thị tùy chỉnh

Inverter Unit Display Board​

In a single-suction system, you typically pick one SST that can satisfy the coldest or most demanding room, then manage warmer rooms by cycling their solenoid valves (and fans/defrost strategy if needed).

Practical guidance: the closer the rooms’ setpoints are to each other, the easier it is to maintain stable control, avoid icing problems, and keep energy use reasonable.

Bước chân 2: Load calculation and equipment sizing

Correct sizing starts with two numbers: (1) each room’s heat load and (2) the maximum simultaneous load when multiple rooms pull down at the same time.

Size each evaporator for its room load and operating temperature, because airflow, coil selection, and refrigerant feed must match that specific space.

Then size the condensing unit for the combined capacity at the selected SST and design ambient, considering that multiple rooms can call together after door openings or during initial pull-down.

Selection must respect the condensing unit manufacturer’s application envelope and installation guidance, because improper application can lead to unstable head pressure control, oil return issues, and nuisance trips.

Bước chân 3: Refrigerant piping layout (multi-evaporator basics)

1) A typical layout uses:

  • One liquid line from the condensing unit that becomes a liquid header, then branches to each evaporator.

  • One suction header that collects suction vapor from each evaporator branch and returns to the compressor.

2) Line sizing: header vs branches

Branch lines should be sized for each evaporator’s capacity, while the main header(S) must be sized for the total combined flow at full load.

Good piping design also aims to keep pressure drops reasonable and maintain refrigerant velocities needed for oil return under both full-load and part-load conditions.

3) Oil return and traps

Oil return is a major design concern because oil circulates with refrigerant and must return to the compressor reliably.
Guidance for suction line “P” traps notes they are used to help oil return in vertical risers and that a trap is required whenever the compressor is above the evaporator, with special considerations like inverted traps for certain suction header configurations.

Hệ thống uốn dầu trở lại

Oil Return​

Cũng, suction lines are commonly pitched in the direction of refrigerant flow to promote oil return, which is emphasized in refrigerant piping design guidance.

4) Insulation and condensation control

Suction lines commonly require insulation to reduce heat gain and prevent condensation (“sweating”), which improves performance and reduces water damage risk around the building.

Bước chân 4: Room-by-room control (thermostat + liquid line solenoid)

To let each cold room operate independently, cài đặt:

  • One thermostat (or electronic room controller) per cold room.

  • One liquid line solenoid valve per evaporator (typically installed in the liquid line feeding the evaporator), controlled by that room’s thermostat.

A solenoid valve is an electronically operated valve used to control flow in a fully open/fully closed mode, making it suitable for on/off control at each evaporator.

When a room reaches setpoint, its thermostat closes the solenoid, stopping refrigerant flow to that evaporator while other rooms can continue running if they still call for cooling.

Expansion valves still matter

Even with solenoid control, each evaporator typically needs a proper refrigerant metering device (commonly a TXV/TEV) selected for refrigerant type and capacity, because stable superheat control depends on correct feed and distribution at the evaporator.

Tính năng TXV

TXV​

Bước chân 5: Pump-down control (protect the compressor)

Pump-down control is widely used with liquid line solenoids because it reduces the chance of liquid refrigerant migrating into the compressor during off cycles and causing flooded starts or oil dilution.

In a pump-down sequence, when the thermostat is satisfied it closes the liquid line solenoid; the compressor continues to run and “pumps” refrigerant from the low side toward the condenser/receiver until suction pressure drops to a low-pressure control cut-out setting.

Key control components include:

  • Liquid line solenoid(S), opened by a cooling demand and closed when satisfied.

  • A properly set low-pressure control near the compressor that shuts the compressor off at the appropriate suction pressure (not “to zero”), which is highlighted as an important detail in pump-down explanations.

Important system requirement: pump-down works properly only when the high-side storage (condenser and/or receiver) can safely hold the system’s refrigerant charge during pump-down, which is noted in pump-down descriptions.

Bước chân 6: Defrost planning for multiple evaporators

Defrost must be planned per cold room because frost formation varies by humidity, door openings, and coil temperature.
Cold storage design guidance describes timer defrost (time initiated/time terminated) as a common method and also discusses demand defrost approaches, highlighting that defrost strategy is a real design decision—not an afterthought.

In multi-room systems, stagger defrost schedules so not all evaporators go into defrost at the same time, which helps maintain suction stability and avoids large temperature swings across the facility.

Bước chân 7: Commissioning checklist (what to verify)

Commissioning a multi-evaporator system is about proving three things: refrigeration tightness, correct refrigerant charge/operating conditions, and correct control behavior per room.

Use a practical checklist:

1. Pressure test and leak check before charging, following the condensing unit manufacturer’s installation/maintenance requirements.

2. Evacuate properly and confirm vacuum holds, because moisture and non-condensables create reliability issues.

3. Charge the system and confirm stable subcooling/superheat per manufacturer guidance, because multi-evaporator systems can be sensitive to charge and feed.

4. Confirm each thermostat opens the correct solenoid and only that room starts cooling, proving room-by-room independence.

5. Test pump-down: close a solenoid, watch suction drop, and verify the low-pressure control shuts the compressor off at the intended cut-out.

6. Test “multiple rooms calling” and “single room calling” modes, because oil return and suction stability must work across part-load operation.

Common mistakes and troubleshooting tips

Mistake 1: Mixing freezer and cooler rooms on a simple shared SST

If a warmer room shares suction pressure with a freezer SST, it can overcool, freeze coils, or require excessive cycling to maintain temperature.

Fix options include separating systems, adding more advanced capacity/pressure regulation controls, or redesigning the architecture to match the application constraints.

Mistake 2: Skipping solenoids (or wiring them wrong)

Without a dedicated solenoid controlled by each room thermostat, refrigerant can feed a satisfied evaporator, leading to temperature overshoot and migration issues.

Verify that each solenoid is correctly oriented and controlled, since the on/off nature of solenoids is central to independent zoning.

van điện từ

Solenoid Valve​

Mistake 3: Poor suction piping (oil return problems)

Oil return issues often show up as noisy operation, high compressor wear, or poor performance during part load when only one small room is calling.

Follow suction line practices such as correct pitch and appropriate traps for risers to help oil return, especially when elevation changes exist.

Mistake 4: Defrost not coordinated

If defrost is poorly scheduled, rooms may warm excessively or the system may behave erratically as multiple evaporators enter defrost simultaneously.

Correct by using a clear defrost plan (timer or demand) and staggering defrosts to match actual frost conditions and room usage.

FAQ

1) Can one condensing unit run two or more cold rooms?

Đúng, one condensing unit can serve multiple evaporators, but the rooms should be temperature-compatible because a simple design usually shares one suction pressure level.

2) Do I need a liquid line solenoid for each cold room?

For independent control, a common approach is one thermostat and one liquid line solenoid per evaporator/room, so each room can stop refrigerant flow when it reaches setpoint.

3) What is “pump-down,” and why is it used?

Pump-down is a control method where solenoid closure stops refrigerant feed and the compressor continues running until a low-pressure control shuts it off, reducing liquid refrigerant migration risk during off cycles.

4) How do I avoid oil return problems in a multi-room system?

Oil return depends on correct suction line sizing, proper pitch, and traps/inverted traps in the right locations, especially with vertical risers and varying load conditions.

dàn nóng nằm phía dưới dàn lạnh

If the number of rooms, target temperatures, and distances from the condensing unit are provided, the post can be upgraded with a “sample piping and controls” section (example layout, valve list, and a commissioning test script) tailored to that scenario.

Phần kết luận

Bringing multiple cold rooms under one condensing unit can be a smart, cost-effective way to build a multi-zone cold storage system—if the design matches the application.

The winning formula is temperature compatibility, correct capacity selection, and a piping layout that supports stable refrigerant flow and reliable oil return. Just as important, each room must have independent control, typically using a room thermostat and a dedicated liquid line solenoid valve, so one room can satisfy without forcing the others to overcool.

When pump-down control, defrost scheduling, and safety controls are planned from the start, you get better temperature stability, fewer nuisance trips, and longer equipment life.

Trước khi cài đặt, validate load assumptions and operating conditions, then commission carefully by testing each room individually and all rooms together.

Done right, one condensing unit can reliably serve multiple cold rooms with simple operation and efficient performance.

Mọi ý kiến?

Chào mừng bạn để lại tin nhắn hoặc đăng lại.

Facebook
Twitter
LinkedIn
Reddit
In

Để lại một câu trả lời

Về công ty chúng tôi

Tập đoàn đường cao tốc Trung Quốc là một sản phẩm HVACR chuyên nghiệp’ nhà sản xuất và bán buôn, chúng tôi tùy chỉnh các sản phẩm và phụ tùng HVACR khác nhau, đặc biệt là các sản phẩm điện lạnh và linh kiện. Chẳng hạn như điều hòa không khí, thiết bị làm lạnh, đơn vị phòng lạnh, máy làm đá, máy hút ẩm, động cơ điện, phụ kiện (máy nén, Bộ trao đổi nhiệt, cuộn dây đồng, van, hộp điều khiển, thiết bị bay hơi) vân vân.

Như đã làm việc trong lĩnh vực HVACR từ 2010, chúng tôi có nhiều kinh nghiệm hơn có thể cung cấp cho bạn các sản phẩm và giải pháp độc đáo, cũng sẽ cung cấp miễn phí suốt đời hỗ trợ kỹ thuật. Nhiệt liệt chào mừng yêu cầu chúng tôi với mẫu của bạn, bản vẽ hoặc thiết kế, mục đích của chúng tôi là biến ý tưởng của bạn thành hiện thực và mang lại lợi ích cho bạn.

Còn gì nữa, cho khách hàng của chúng tôi, chúng tôi sẽ cung cấp các sản phẩm khác, xác minh nhà cung cấp, đàm phán với họ với phí miễn phí cho bạn.

về tác giả

Bức hình của Vic Cheung
Vic Cheung

CHÀO, tôi là Vic! Bắt đầu làm việc trong lĩnh vực HVACR từ 2008, sản phẩm chính của chúng tôi bao gồm: điều hòa không khí, hệ thống lạnh phòng lạnh, máy làm lạnh nước, máy làm đá, máy khử nước thương mại, máy hút ẩm, bơm nhiệt, động cơ điện, và tất cả các phụ kiện. Kể từ khi gia nhập China Speedway Group vào năm 2012, Tôi đã làm việc ở đây hơn 10 năm, là tổng giám đốc của bộ phận xuất khẩu, chúng tôi đã thành lập 50+ đại lý ở các quốc gia và khu vực khác nhau.
Theo kinh nghiệm của chúng tôi và hỗ trợ kỹ thuật mạnh mẽ, chúng tôi có thể giải quyết vấn đề của bạn sau khi bạn có, và kỹ sư trưởng của chúng tôi đã làm việc trong lĩnh vực HVACR kể từ đó 1997. Tôi rất tự hào về kiến ​​thức của chúng tôi ngày càng phổ biến không chỉ cho kỹ sư, và cho người mới kinh doanh HVACR, những người yêu thích tự làm. Hy vọng bạn thích bài viết của chúng tôi, nếu có bất kỳ câu hỏi hoặc nhận xét nào, vui lòng gửi cho tôi thông tin tiếp thị tại cn-beyond.com

Tất cả những bài viết

Liên hệ chúng tôi

Chỉ cần điền địa chỉ email của bạn, số điện thoại và mô tả ngắn gọn về yêu cầu của bạn trong biểu mẫu này. Chúng tôi sẽ liên lạc với bạn trong vòng 24 giờ.

Liên hệ chúng tôi

Sẵn sàng bắt đầu dự án của bạn với chúng tôi?

Hợp tác với chúng tôi để nâng cao uy tín thương hiệu của bạn, có được trải nghiệm ấn tượng để khách hàng nhớ đến bạn suốt đời, và giúp bạn nổi bật trong thị trường cạnh tranh !

Đừng bỏ lỡ Đối tác OEM tốt nhất!

Sẵn sàng làm việc với chúng tôi?

Trải nghiệm sự khác biệt của chúng tôi và Thực hiện bước đầu tiên hướng tới một tương lai tốt đẹp hơn cho doanh nghiệp của bạn!
Seraphinite AcceleratorOptimized by Seraphinite Accelerator
Turns on site high speed to be attractive for people and search engines.