At CHINA SPEEDWAY, we provide custom refrigeration products solutions for our clients. Recently,we have client buying cold room unit, worked for a cold room project with super longer distance between cold room and outdoor condensing unit. 記事上で, we will give you actual example how did we work in this cold room project and keep stored products fresh and durable, so as a reference for customers who need similar cold room projects.
Clients specifications
Clients need to accurately control the cold room temperture scope to avoid any damage for the goods, here are the details about this cold room project.
Country: アラブ首長国連邦
周囲温度: Max 50~55°C ( Maximum 15 days for total in summer)
冷蔵室のサイズ: 7X3.5X2.5m (length x width x height)
Cold room application: Store medicine
寒い室温: Constant 2~8°C
Inverter condensing unit location: On the roof (totally six floors)
Cold room location: 地下
Direct distance between roof and basement: 25メートル
Basic Solution
Inverter Condensing unit (outdoor unit): 5HP(馬力), 220Ⅴ, 1phase 50Hz, R404 refrigerant. with oil return bend protection system, with 50m cable connect to display screen board. As max ambient temperature is 50~55°C, so must use bigger size condensing unit (use 5HP but not 4HP), also need a shelder to lower the temperature around the unit.
Evaporator unit (室内機): 6.5HP 220V, 1 phase 50Hz
冷蔵室パネル: 150mm thickness PU sandwich panel with 0.35mm galvanized steel
冷蔵室のドア: 150mm thickness PU sandwich panel with 10cm height threshold ( for better airtightness), 冷蔵室のサイズ–1.8×0.9メートル (height x width)
Cold room door with threshold
Specific Solution
1. Use oil return bend system ( make several oil return bends when the pipe installation) , max preparing 50m cable to avoid any short of length, see the draft at below:
Pipe Installation Drawing
2. Prepare 2 sets refrigeration equipments ( each set included 1pc condensing unit and 1pc evaporator unit), to avoid any sudden damage.
3. Prepare a plastic air stripe curtain to avoid any cooling air to waste.
4. Minimize the installation length, because more longer means more chance to loss cooling air.
5. Use sealant to get better airtightness, because room temperature need constant 2~8°C
6. Prepare a 20~25kva diesel generator (which can supply both 220V and 380V) for backup when any sudden outage.
7. Use a window balance with 220V 50HZ to balance room inside and outside pressure.
8. Use one or two LED cold room light to keep the light clearly inside of the cold room.
9. Use LED display screen board for inverter condensing unit to monitor the cold room temperature in real time.
LED Display Screen Board
Need custom cold room solution?
At “CHINA SPEEDWAY”, we are experts in providing custom cold room solution for different applications. Room temperature can be +15~-40°C, if you need another special temperature, can show us all requirements accordingly.
We will support you how to make specifically installation and provide drawings for cold room panel assembly, meanwhile give you all tips about cold room working properly and last longer lifetime.
Feel free to contact us for more details or to discuss your specific needs. We look forward to helping you optimize your systems with high-quality, precision-engineered cold room solutions.